Panel Mount Model |
Wall Mount Model |
Integral Mount |
Pipe Mount |
| Features |
- 2 Line Backlit LCD Display
- Rate of flow, Total flow in separate line
- Versatile Mounting – Pipe / Wall / Panel / Integral Mounting
- Programmable Relay Outputs
- 4-20mA Outputs
- Suitable for line sizes from ½’’ to 48’’
- Can be used for clean water –like liquids which may be acidic or alkaline
- Accurate upto + / - 1% of full scale reading
- Microprocessor based signal processing
- Easy on – site re-calibration and programmable cut-off settings
- Complete elimination of downtime with the addition of wet Tap Valve Assembly
- Pulsed output for Dosing applications
|
PRINCIPLE OF OPERATION
|
Paddle wheel flow meters belong to the category of insertion type flow meters.
The rotating paddle wheel generates a signal in proportion to the velocity of the moving fluid, which is read in terms of the flow rate. Because the pipe's cross-sectional area is known and remains fixed the average velocity is an indication of the flow rate. |
| Flow Range |
0.5m/sec to 5m/sec |
| Max.Op.Temperature |
70 deg c |
| Max.Op.Pressure |
10kg/sq cm |
| Power Supply |
230V ~ AC/24C DC |
| Pressure Drop |
<0.1 kg/ sq.cm |
Material Of Construction
|
Transducer Housing
|
POLYPROPYLENE |
| O-rings |
NEOPRENE |
| Shaft |
SS316/ HASTALLOY C/PVDF |
| Rotor |
PVDF |
| Maximum %solids |
1% of fluid volume, non-abrasive, non-magnetic,
<100micron in diameter and length |
| Max.Viscosity |
1 Cp(water) upto 5Cp above1.5m/sec |
| Output |
2-Line 16 Character Backlit LCD Display |
| Register |
Rate of flow – m³/hr,
Total flow –m³ |
| Standard Cable Length |
1.5 mtrs power supply cable for field-mounted versions and 10 mtrs signal transmission cable for panel-mounted versions |
| Process Connection |
ABS TEE/PP wafer drilled as per BS10 Table E/ANSI B16.5 / SS stub / Glue-on PVC saddle |
INSTALLATION FITTINGS
|
 |
All installation fittings are supplied along with the flow sensor. The sensor my be installed in a ABS TEE / PP wafer drilled as per Bs10 TABLE E OR ANSI B16.5 standards or a Glue –on PVC saddle or a SS stub welded to a MS / SS plate.
|
Low Cost OEM Model
|
 |
Features
|
| Indication |
Rate of Flow indication only |
| Model No. |
RFI 100T |
| Panel Cut-out Dim . |
90mm * 42mm |
| Output |
1 Line 5 Digit LED Display |
| Register |
Flow Rate - m³/hr |
ADD –ON FEATURES
|
 |
RELAY OUTPUT |
230 VAC, 1A (Resistive load only) max.with 1NO and 1 NC contact. 1 Or 2 Relay outputs can be given for giving a signal based on flow rate or total flow or both depending upon the requirements. |
INTERFACING WITH PLC |
An open collector pulse output or a 4-20 mA signal can be provided for interfacing with a PLC or connecting to Recorders. |
DOSING APPLICATION |
Programmable pulsed output available |
THE DOWNTIME ELIMINATOR WET TAP VALVE ASSEMBLY |
You can completely eliminate downtime resulting from flow sensor maintenance, with the simple addition of the Wet Tap Valve assembly. Should a sensor, rotor, or O-ring need to be replaced, the wet tap assembly provides a safe and fast method of removing a specially extended sensor from your pipe without system shutdown. |
|